Investigation on the insulation resistance characteristics of low voltage cable

17Citations
Citations of this article
34Readers
Mendeley users who have this article in their library.

Abstract

This study evaluated the insulation resistance characteristics of TFR-8 (Tray Frame Retardant power cable for fire service) and VCTF (Light PVC Sheathed Circular Cord) cables under external flame, over-current, and accelerated degradation tests. In the accelerated degradation test of the cable, aging times of 10, 20, 30, and 40 years were tested according to a temperature derived using the Arrhenius equation. The insulation resistance of the TFR-8 cables was reduced from a maximum of 7.5 T ohm to 0.008 T ohm during the flame contact and recovered to its original state after cooling. However, dielectric breakdown occurred in the VCTF cable during flame contact and the cable did not return to its original state, even after cooling. In the forced convection oven test, the insulation resistance of the cable was reduced at 160 °C, whereas the insulation resistance of the cable was reduced at 125 °C in the over-current test. This result implied that the over-current had a greater impact than did heat applied externally on the degradation of the cable insulator. In the accelerated degradation tests from 10-30 years, the TFR-8 cable did not show any reduction in insulation resistance at room temperature. However, after an induced aging time of 40 years, the cable showed a rapid reduction in insulation resistance at room temperature.

References Powered by Scopus

A contribution to the study of aging of XLPE insulated cables

44Citations
N/AReaders
Get full text

Electrical characterization of extruded DC cable insulation - The challenge of scaling

30Citations
N/AReaders
Get full text

Insulation performance evaluation of HV AC/DC XLPE cables by 0.1 Hz tan δ test on circumferentially peeled samples

29Citations
N/AReaders
Get full text

Cited by Powered by Scopus

Influence of thermal aging on the combustion characteristics of cables in nuclear power plants

19Citations
N/AReaders
Get full text

Multiscale Analysis of the Aging Process of Cable Insulation

13Citations
N/AReaders
Get full text

Digital twin-based degradation prediction for train electro-pneumatic valve

9Citations
N/AReaders
Get full text

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Cite

CITATION STYLE

APA

Kang, S. D., & Kim, J. H. (2020). Investigation on the insulation resistance characteristics of low voltage cable. Energies, 13(14). https://doi.org/10.3390/en13143611

Readers' Seniority

Tooltip

PhD / Post grad / Masters / Doc 5

50%

Lecturer / Post doc 3

30%

Researcher 2

20%

Readers' Discipline

Tooltip

Engineering 9

64%

Energy 4

29%

Materials Science 1

7%

Save time finding and organizing research with Mendeley

Sign up for free